Description
range of product |
Modicon Quantum is an is an automation platform.
|
|
---|---|---|
product or component type |
AC discrete output modules.
|
|
discrete output number |
16
|
group of channels |
4 groups of 4 channels.
|
|
---|---|---|
supply frequency |
47…63 Hz.
|
|
voltage drop |
1.5 V
|
|
discrete output voltage |
83.253 V AC.
|
|
addressing requirement |
1 output word.
|
|
absolute maximum output |
300 Vrmsfor 10 s AC.
400 Vrms, 1 cycle AC. |
|
maximum load current |
16 ARMs per module.
2 mA rms, 115 V off-state leakage per output. 2.5 mA rms, 230 V off-state leakage per output. 3 A rms, 170–253 V per output. 4 A rms, 85…132 V per output 4 RMs per group |
|
surge current |
<= 10 A during 3 cycles per point.
<= 20 A during 2 cycles per point. <= 25 A during 3 cycles per group. <= 30 A during 1 cycle per point. <= 30 A during 2 cycles per group. <= 45 A during 1 cycle per group. |
|
dV/dt |
400 V/ms.
|
|
response time |
<= 0.5 ms from state 0 to state 1.
<= 0.5 ms from state 1 to state 0. |
|
fault indication |
Loss of field power
Blown fuse.. |
|
protection type |
Internal by RC filter.
Internal output protection by 5 A fuse. |
|
power dissipation |
1.85 + (1.1 V x total module load current).
|
|
marking |
CE
|
|
local signalling |
1 LED green bus communication is present (active).
1 LED red external fault detected (F). 16 LEDs have green input status. |
|
bus current requirement |
350 mA.
|
|
module format |
Standard.
|
|
product weight |
0.99 lb (US) (0.45 kg).
|
product certifications |
CUL
FM Class 1 Division 2. |
|
---|---|---|
standards |
UL 508
CSA C22.2 No. 142. |
|
electromagnetic compatibility |
Electrostatic discharge immunity test (test level: 4 kV, contact discharge) conforming to IEC 801-2.
Electrostatic discharge immunity test (test level: 8 kV, air discharge) conforming to IEC 801-2. Susceptibility to electromagnetic fields (test level: 10 V/m, 80…1000 MHz) conforming to IEC 801-3. |
|
ambient air temperature for operation |
32…140 °F (0…60 °C).
|
|
ambient air temperature for storage |
-40.185 °F (-40.85 °C).
|
|
relative humidity |
95% without condensation.
|
|
operating altitude |
<= 16404.2 ft (5000 m).
|
Category |
18155: Quantum I/O & Power Supplies.
|
|
---|---|---|
Discount Schedule |
PC21.
|
|
GTIN |
00785901793809.
|
|
Nbr. of units in pkg. |
1
|
|
Package weight(Lbs) |
1.4000000000000001.
|
|
Returnability |
Y
|
|
Country of origin |
CN.
|
The 140DAO84210 is a discrete output module from the Modicon Quantum series by Schneider Electric, designed for use in advanced industrial automation systems. This module is engineered to provide precise control of digital output signals, making it a critical component in a range of industrial applications where reliable and efficient output management is essential.
Key Features
- Output Channels: The 140DAO84210 module features 16 discrete output channels. This configuration allows it to manage multiple output signals simultaneously, making it suitable for complex automation systems that require extensive control over digital output devices.
- Output Voltage and Current: The module operates with a standard output voltage of 24V DC. Each channel is capable of handling up to 0.5 A of current. This makes it versatile for controlling various field devices such as relays, solenoids, and actuators, which are commonly used in industrial processes.
- Electrical Isolation: A critical feature of the 140DAO84210 is its electrical isolation between the output channels and the internal circuitry. This isolation is crucial for protecting the module from electrical noise and potential damage caused by voltage spikes or transients. It helps maintain the reliability and stability of the control system.
- Response Time: The module is designed to provide rapid response times, ensuring that output signals are processed quickly and accurately. This feature is important for applications where timely control of output devices is necessary to maintain efficient and safe operation.
- Diagnostic and Status Indicators: The 140DAO84210 includes diagnostic features and status indicators that provide real-time feedback on the operational status of each output channel. These indicators help in monitoring the health of the module and facilitate troubleshooting in case of issues, ensuring that any problems can be quickly identified and addressed.
- Signal Filtering: To enhance the accuracy of output signals and reduce the impact of electromagnetic interference, the module incorporates signal filtering capabilities. This feature ensures that the output signals are clean and reliable, which is essential for maintaining the integrity of the control system.
- Form Factor and Installation: The 140DAO84210 is designed to fit into a Modicon Quantum rack system. Its compact form factor allows for easy integration into existing setups. Installation involves securely mounting the module in the rack and making the necessary electrical connections, which is straightforward and efficient.
Applications
The 140DAO84210 module is highly versatile and can be used in various industrial settings.
- Manufacturing Automation: In manufacturing environments, the module controls output devices such as solenoids and relays that manage machinery and production lines. This enables precise automation and control, enhancing overall efficiency and productivity.
- Process Control: For process industries, including chemical and pharmaceutical sectors, the module manages outputs that control critical process components such as valves, pumps, and mixers. This ensures accurate regulation and monitoring of process variables.
- Building Automation: In building management systems, the module interfaces with devices like lighting systems, HVAC controls, and security systems. It allows for centralized control and monitoring of building infrastructure, contributing to improved operational efficiency and user comfort.
Installation and Maintenance
Installation: The 140DAO84210 module is designed for seamless integration into the Modicon Quantum rack system. Installation involves placing the module into the rack and connecting it to the relevant field devices. Proper installation ensures that the module functions correctly and integrates smoothly with other system components.
Maintenance: Routine maintenance includes monitoring the diagnostic indicators and performing regular checks to ensure that the module operates properly. The diagnostic features assist in quickly identifying and resolving issues, minimizing downtime, and maintaining system reliability.