Description
Description
Analog Input Module Modicon Quantum – 8 I Thermocouple
range of product | Modicon Quantum automation platform | |
---|---|---|
product or component type | Analogue input module | |
type of filter | Notch filter – 3 dB at 50/60 Hz Single pole low pass – 3 dB at 20 Hz |
analogue input number | 8 | |
---|---|---|
addressing requirement | 10 input words | |
analogue input type | Thermocouple – 210…760 °C thermocouple J Thermocouple – 270…1000 °C thermocouple E Thermocouple – 270…1370 °C thermocouple K Thermocouple – 270…400 °C thermocouple T Thermocouple – 50…1665 °C thermocouple R Thermocouple – 50…1665 °C thermocouple S | |
analogue input resolution | 16 bits | |
input impedance | > 1 MOhm | |
absolute accuracy error | +/- 2 °C plus + 0.1 % of reading thermocouple J +/- 2 °C plus + 0.1 % of reading thermocouple K +/- 2 °C plus + 0.1 % of reading thermocouple T +/- 4 °C plus + 0.1 % of reading thermocouple R +/- 4 °C plus + 0.1 % of reading thermocouple S +/- 2 °C plus + 0.1 % of reading thermocouple E | |
linearity error | 1 °C, 0.1 °C, 1 F, 0.1 F – 210…760 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…1000 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…1370 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 270…400 °C 1 °C, 0.1 °C, 1 F, 0.1 F – 50…1665 °C | |
accuracy drift according to temperature | 0.15 µV/°C + 0.0015 % of reading/°C max low level voltage | |
common mode rejection | > – 120 dB 50/60 Hz | |
isolation between channels and bus | 1780 V AC for 60 s 2500 V DC for 60 s | |
isolation between channels | 220 V AC 300 V DC | |
update time | 1000 ms | |
fault type | Broken wire Overtacking scale | |
marking | CE | |
cold junction compensation | Internal 32…140 °F (0…60 °C) | |
local signalling | 1 LED green bus communication is present (Active) 1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault | |
bus current requirement | 280 mA | |
power dissipation in W | 1.5 W | |
module format | Standard | |
product weight | 0.66 lb(US) (0.3 kg) |
standards | CSA C22.2 No 142 UL 508 | |
---|---|---|
product certifications | CUL FM Class 1 Division 2 | |
resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 | |
resistance to electromagnetic fields | 9.14 V/yd (10 V/m) 80…1000 MHz conforming to IEC 801-3 | |
ambient air temperature for operation | 32…140 °F (0…60 °C) | |
ambient air temperature for storage | -40…185 °F (-40…85 °C) | |
relative humidity | 95 % without condensation | |
operating altitude | <= 16404.2 ft (5000 m) |