170AMM09000 – distributed analog/discrete I/O
Original price was: $1,274.00.$980.00Current price is: $980.00.
The 170AMM09000 distributed I/O module by Schneider Electric combines analog and discrete inputs/outputs, offering 8 analog inputs, 2 analog outputs.
1 in stock
Free shipping on orders over $5000!
- Satisfaction Guaranteed
- No Hassle Refunds
- Secure Payments
Description
range of product |
Modicon Momentum is an automation platform.
|
|
---|---|---|
product or component type |
Analog, discrete I/O base.
|
|
group of channels |
1 group of 2 discrete outputs.
1 group of 4 discrete inputs. 1 group of 4 analog differential inputs. 1 group of 2 analog outputs. |
|
analogue input range |
+/- 10 V.
+/- 20 mA. +/- 5 V. 1…5 V. 4…20 mA. |
|
analogue input type |
Differential
|
|
analogue input resolution |
12 bits, 1…5 V.
12 bits, 4…20 mA. 13 bits +/- 20 mA. 13 bits +/- 5 V. 14 bits +/- 10 V. |
|
discrete input voltage |
24 V DC.
|
|
analogue output range |
+/- 10 V, 12 bits.
0…20 mA, 12 bits. |
|
discrete output voltage |
<= 30 V.
|
|
output short-circuit protection |
With discrete output.
|
|
output overload protection |
With discrete output.
|
discrete input number |
4 conforms to IEC 1131-2 Type 1.
|
|
---|---|---|
[Us] rated supply voltage |
24 VDC.
|
|
conversion consistency |
+/- 0.02 % +/- 10 V analogue input circuit.
+/- 0.04 % +/- 20 mA analogue input circuit. +/- 0.04 % +/- 5 V analogue input circuit. +/- 0.04 % 1…5 V analogue input circuit. +/- 0.04% 4…20 mA analogue input circuit. |
|
common mode rejection |
> 54 dB analogue input circuit.
|
|
input voltage limits |
< 30 V
|
|
discrete input logic |
Positive
|
|
voltage state 0 guaranteed |
-3…5 V for discrete input.
|
|
voltage state 1 guaranteed |
11–30 V for discrete input.
|
|
current state 0 guaranteed | ||
current state is guaranteed |
>= 2.5 mA (discrete input).
|
|
input overvoltage protection |
-50…50 V <= 100 s analogue input circuit.
-30…30 V 24 V analogue input circuit. |
|
input resistance |
1 MOHm analogue input circuit.
4 kOhm discrete input |
|
output load |
<= 600 Ohm 0…20 mA analogue output.
>= 3 kOhm +/- 10 V analogue output. |
|
conversion time |
1 ms analogue output.
10 ms analogue input circuit. |
|
conversion error |
+/- 0.35 % +/- 10 V 25 °C analogue output.
+/- 0.35 % 0…20 mA, 25 °C analogue output. +/- 0.70 % +/- 10 V 60 °C analogue output. +/- 0.70% 0…20 mA, 60 °C analogue output. 0,0008 +/- 10 V, 25 °C, analogue input circuit. 0,0015 +/- 10 V, 60 °C analogue input circuit. 0,0016 +/- 20 mA, 25 °C, analogue input circuit. 0,0016 +/- 5 V, 25 °C, analogue input circuit. 0,0016 1…5 V 25 °C analogue input circuit. 0,0016 4…20 mA 25 °C analogue input circuit. 0,003 +/- 20 mA, 60 °C analogue input circuit. 0,003 +/- 5 V, 60 °C analogue input circuit. 0,003 1…5 V 60 °C analogue input circuit. 0,003 4…20 mA, 60 °C analogue input circuit. |
|
fail state |
For an analog input circuit, hold.
For the analog input circuit, reset to zero. |
|
discrete output type |
Transistor.
|
|
discrete output logic | ||
discrete output current |
1 A per point.
2 A per group. 2 A per module. |
|
maximum leakage current |
1 mA DC, 24 V discrete output.
|
|
maximum voltage drop |
<0.5 V 1 A at state on discrete output.
|
|
operating rate |
100 cyc/s resistive, 1 A discrete output.
1000 cyc/h inductive 1 A discrete output. 8 cyc/s tungsten, <2.4 W discrete output. |
|
response time |
< 0.1 ms from state 0 to state 1 for discrete output.
< 0.1 ms from state 1 to state 0 for discrete output. 2.2 ms from state 0 to state 1 for discrete input. 3.3 ms from state 1 to state 0 for discrete input. |
|
isolation voltage |
500 V (duration = 1 min) between analogue I/O and operating voltage.
500 V (duration = 1 min) between operating voltage and I/O from ground. |
|
maximum power dissipation in W |
6 W
|
|
marking |
CE
|
|
local signalling |
8 LEDs for channel status.
|
|
electrical connection |
2 connectors for removable terminal blocks.
|
|
current consumption |
<= 350 mA at 24 V DC.
200 mA at 24 V DC. |
|
depth |
47.5 mm
|
|
height |
125 mm
|
|
width |
141.5 mm
|
|
net weight |
0.24 kg
|
product certifications |
UL.
CSA FM Class 1 Division 2. |
|
---|---|---|
protective treatment |
TC
|
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2.
8 kV on air, conforming to IEC 801-2. |
|
resistance to electromagnetic fields |
10 V/m 80…1000 MHz, conforming to IEC 801-3.
|
|
ambient air temperature for operation |
0…60 °C.
|
|
ambient air temperature for storage |
-40…85 °C.
|
|
relative humidity |
95% without condensation.
|
|
operating altitude |
<= 5000 m.
|