Description

Main
range of product
Altistart 48.
product or component type
product destination
Asynchronous motors.
product-specific application
Heavy-duty industry and pumps.
device’s short name
ATS48.
power supply voltage
208…690 V – 15…10 %.
motor power kW
160 kW at 230 V for severe applications.
315 kW at 400 V for severe applications.
355 kW at 400 V for standard applications.
355 kW at 440 V for severe applications.
400 kW at 440 V for standard applications.
400 kW at 500 V for severe applications.
400 kW at 525 V for severe applications.
560 kW at 660 V for severe applications.
560 kW at 690 V for severe applications.
630 kW at 660 V for standard applications.
630 kW at 690 V for standard applications.
motor power hp
200 hp at 208 V for standard applications.
200 hp at 230 V for severe applications.
250 hp at 230 V for standard applications.
400 hp at 460 V for severe applications.
500 hp at 460 V for standard applications.
500 hp at 575 V for severe applications.
600 hp at 575 V for standard applications.
power dissipation in W
1731 W for standard applications.
1958 W for standard applications.
utilisation category
AC-53A.
type of start
Start with torque control (currently limited to 5 inches).
Icl nominal current
660 A for connection in the motor supply line for severe applications.
660 A for connection in the motor supply line for standard applications.
Complementary
assembly style
With heat sink.
function available
External bypass (optional).
power supply frequency
50…60 Hz, 5…5 %.
power supply frequency limits
47.5…63 Hz.
device connection
In the motor supply line.
discrete output number
2
discrete output type
(LO1) logic output 0 V common configurable.
(LO2) logic output 0 V common configurable.
(R1) relay outputs fault relay NO.
(R2) relay outputs end of starting relay NO.
(R3) relay outputs motor-powered NO.
output absolute accuracy precision
+/- 5 %
minimum switching current
10 mA at 6 V DC for relay outputs.
maximum switching current
Logic output: 0.2 A at 30 V DC.
Relay outputs 1.8 A at 230 V AC. inductive load, cos phi = 0.5 20 ms.
Relay outputs 1.8 A at 30 V. DC inductive load, cos phi = 0.5 ms.
discrete input number
5
discrete input type
PTC, 750 Ohm at 25 °C.
(Stop, Run, LI3, LI4) logic, <= 8 mA, 4300 Ohm.
discrete input voltage
24 V <= 30 V.
discrete input logic
Positive logic Stop, Run, LI3, .LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA.
starting current
0.4…1.3 Icl adjustable.
analogue output type
Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm.
communication port protocol
Modbus
connector type
1 RJ45
communication data link
Serial
physical interface
RS485 multidrop.
transmission rate
4800, 9600 or 19200 bps.
max nodes number
31
protection type
Phase failure: line.
Thermal protection: motor.
Thermal protection: starter.
marking
CE
operating position
Vertical +/- 10 degree.
height
670 mm
width
400 mm
depth
300 mm
net weight
51.4 kg
Motor power range: AC-3
110…220 kW at 200…240 V, 3 phases.
250…500 kW at 380…440 V in 3 phases.
motor starter type
Soft starter
Environment
electromagnetic compatibility
Conducted and radiated emissions level A. conforming to IEC 60947-4-2.
Damped oscillating waves, level 3, conforming to IEC 61000-4-12.
Electrostatic discharge level 3 conforms to IEC 61000-4-2.
Immunity to electrical transients, level 4 conforming to IEC 61000-4-4.
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3.
Voltage/current impulse level 3 conforming to IEC 61000-4-5.
standards
EN/IEC 60947-4-2.
product certifications
SEPRO
DNV
CCC
NOM 117
CSA
UL
GOST
TCF
C-Tick
noise level
55 dB
relative humidity
0…95 % without condensation or dripping water. conforming to EN/IEC 60068-2-3.
ambient air temperature for operation
40…60 °C (with current derating of 2 % per °C).
-10…40 °C (without derating).
ambient air temperature for storage
-25…70 °C.
operating altitude
<= 1000 m without derating.
> 1000…2000 m with current derating of 2.2 % per additional 100 m.