Sale!

LC1D40AU7 – TeSys D contactor-3P(3 NO)-AC-3-<= 440 V

Original price was: $78.00.Current price is: $60.00.

2 in stock

Category:

Description

 

Main
rangeTeSys.
TeSys Deca.
range of productTeSys D.
TeSys Deca.
product or component typeContactor.
device short nameLC1D.
contactor applicationMotor control.
Resistive load.
utilisation categoryAC-4..
AC-1.
AC-3.
AC-3e.
poles description3P.
[Ue] rated operational voltagePower circuit: <= 690 V AC 25…400 Hz.
Power circuit: <= 300 V DC.
[Ie] rated operational current60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit.
40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit.
40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit.
[Uc] control circuit voltage240 V AC 50/60 Hz.
Complementary
motor power kW18.5 kW at 380…400 V AC 50/60 Hz (AC-3).
11 kW at 220…230 V AC 50/60 Hz (AC-3).
22 kW at 415…440 V AC 50/60 Hz (AC-3).
22 kW at 500 V AC 50/60 Hz (AC-3).
30 kW at 660…690 V AC 50/60 Hz (AC-3).
9 kW at 400 V AC 50/60 Hz (AC-4).
18.5 kW at 380–400 V AC 50/60 Hz (AC-3e).
11 kW at 220…230 V AC 50/60 Hz (AC-3e).
22 kW at 415…440 V AC 50/60 Hz (AC-3e).
22 kW at 500 V AC 50/60 Hz (AC-3e).
30 kW at 660…690 V AC 50/60 Hz (AC-3e).
motor power hp5 hp at 230/240 V AC 50/60 Hz for 1 phase motors.
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors.
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors.
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors.
3 hp at 115 V AC 50/60 Hz for 1 phase motors.
30 hp at 460/480 V AC 50/60 Hz for 3 phases motors.
compatibility codeLC1D.
pole contact composition3 NO.
contact compatibilityM2.
protective coverWith.
[Ith] conventional free air thermal current10 A (at 60 °C) for the signaling circuit.
60 A (at 60 °C) for the power circuit.
Irms rated making capacity140 A AC for signalling circuits conforming to IEC 60947-5-1.
250 A DC for the signaling circuit conforming to IEC 60947-5-1.
800 A at 440 V for a power circuit conforming to IEC 60947.
rated breaking capacity800 A at 440 V for a power circuit conforming to IEC 60947.
[Icw] rated short-time withstand current320 A, 40 °C, 10 s for the power circuit.
720 A, 40 °C, 1 s for the power circuit.
72 A, 40 °C, 10 min for the power circuit.
165 A 40 °C – 1 min for power circuit.
100 A – 1 s for the signaling circuit.
120 A to 500 ms for the signaling circuit.
140 A to 100 ms for the signaling circuit.
associated fuse rating10 A gG for the signaling circuit conforming to IEC 60947-5-1.
80 A gG at <= 690 V coordination type 1 for the power circuit.
80 A gG at <= 690 V coordination type 2 for the power circuit.
average impedance1.5 mOhm (60 A, 50 Hz) for a power circuit.
power dissipation per pole2.4 W AC-3.
5.4 W AC-1.
2.4 W AC-3e.
[Ui] rated insulation voltagePower circuit: 600 V CSA-certified.
Power circuit: 600 V UL certified.
Signaling circuit: 690 V, conforming to IEC 60947-1.
Signaling circuit: 600 V CSA-certified.
Signalling circuit: 600 V UL certified
Power circuit: 690 V, conforming to IEC 60947-4-1.
overvoltage categoryIII
pollution degree3
[Uimp] rated impulse withstand voltage6 kV, conforming to IEC 60947.
safety reliability levelB10d = 1369863 cycles per contactor with a nominal load. conforming to EN/ISO 13849-1.
B10d = 20000000 cycles of contactor with mechanical. load conforming to EN/ISO 13849-1.
mechanical durability6 Mcycles
electrical durability1.4 Mcycles 60 A AC-1 at Ue <= 440 V.
1.5 Mcycles 40 A AC-3 at Ue <= 440 V.
1.5 Mcycles 40 A AC-3e at Ue <= 440 V.
control circuit typeAC at 50/60 Hz.
coil technologyWithout a built-in suppressor module.
control circuit voltage limits0.3–0.6 Uc (-40–70 °C): drop-out AC 50/60 Hz.
0.8…1.1 Uc (-40…60 °C): operational AC 50 Hz.
0.85…1.1 Uc (-40…60 °C): operational AC 60 Hz.
1…1.1 Uc (60…70 °C): operational AC 50/60 Hz.
inrush power in VA140 VA, 60 Hz, cosphi 0.75 (at 20 °C).
160 VA, 50 Hz, cosphi 0.75 (at 20 °C).
hold-in power consumption in VA13 VA, 60 Hz, cos phi 0.3 (at 20 °C).
15 VA, 50 Hz, cos phi 0.3 (at 20 °C).
maximum operating rate3600 cyc/h, 60 °C.
tightening torqueControl circuit: 1.7 N.m. on screw clamp terminals with a screwdriver flat Ø 6 mm.
Control circuit: 1.7 N.m. on screw clamp terminals with screwdriver Philips No. 2.
Power circuit: 8 N.m – on EverLink BTR screw. connectors – cable 25…35 mm² hexagonal screw head 4 mm.
Power circuit: 5 N.m – on EverLink BTR screw. connectors – cable 1…25 mm² hexagonal screw head 4 mm.
Control circuit: 1.7 N.m. on screw clamp terminals, with screwdriver pozidriv No. 2.
Power circuit: 2.5 N.m. on screw clamp terminals, with screwdriver pozidriv No. 2.
auxiliary contact composition1 NO + 1 NC.
auxiliary contacts typeType mechanically linked: 1 NO + 1 NC, conforming to IEC 60947-5-1.
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25…400 Hz.
minimum switching voltage17 V for the signaling circuit.
minimum switching current5 mA for the signaling circuit.
insulation resistance> 10 MOhm for the signaling circuit.
non-overlap time1.5 ms on de-energization between NC and NO contact.
1.5 ms on energization between NC and NO contact.
mounting supportPlate.
Rail.
Environment
standardsCSA C22.2 No. 14.
EN 60947-4-1.
EN 60947-5-1.
IEC 60947-4-1.
IEC 60947-5-1.
UL 508.
IEC 60335-1.
product certificationsCSA.
CCC.
UL.
GOST.
IP degree of protectionIP20 front face conforms to IEC 60529.
climatic withstandConforming to IACS E10.
conforming to IEC 60947-1 Annex Q category D.
operating altitude0…3000 m.
fire resistance850 °C, conforming to IEC 60695-2-1.
flame retardanceV1 conforms to UL 94.
height122 mm.
width55 mm.
depth120 mm.
net weight0.85 kg.
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.2 cm.
Package 1 Width13.7 cm.
Package 1 Length15.5 cm.
Package 1 Weight927.0 g.
Unit Type of Package 2S02.
Number of Units in Package 210
Package 2 Height15.0 cm.
Package 2 Width30.0 cm.
Package 2 Length40.0 cm.
Package 2 Weight9.969 kg