Sale!

PM710MG – power meter PM710 – basic readings

Original price was: $1,105.00.Current price is: $850.00.

The PM710MG is a power meter designed for accurate and reliable measurement of electrical parameters in various industrial and commercial settings.

15 in stock

Free shipping on orders over $5000!

  • Check Mark Satisfaction Guaranteed
  • Check Mark No Hassle Refunds
  • Check Mark Secure Payments
GUARANTEED SAFE CHECKOUT
  • Visa Card
  • MasterCard
  • American Express
  • Discover Card
  • PayPal

Description

 

Main
range of product
PowerLogic PM700.
device’s short name
PM710.
product or component type
Power meter.
Complementary
power quality analysis
Total harmonic distortion.
type of measurement
Current.
Voltage.
Frequency.
Power factor total.
Apparent power total.
Active power total.
Reactive power total.
Apparent power per phase.
Active power per phase.
Reactive power per phase.
Energy.
supply voltage
125–250 V DC.
115…415 V AC 45…65 Hz.
network frequency
45…65 Hz.
maximum power consumption in VA
5 VA
display type
Backlit LCD..
display resolution
6 lines.
sampling rate
32 samples/cycle.
measurement current
5 A.
1 A.
input type
Current: 0.005…6 A (impedance <= 0.1 Ohm).
measurement voltage
10…480 V AC 45…65 Hz, phase to phase.
10…277 V AC 45…65 Hz phase to neutral.
measurement accuracy
Power: 1%.
Current 0.5% 1…6 A.
Voltage: 0.5%, 50… 227 V.
Frequency: 0.02 Hz, 45–65 Hz.
Power factor: 0.0034 1A to 6A and from -0.5. to +0.5.
accuracy class
Class 2 reactive energy conforms to IEC 62053-23.
Class 1 active energy conforms to IEC 62053-21.
communication port protocol
Modbus 19.2 kbauds.
communication port support
RS485.
data recording
Min/max of instantaneous values.
Environment
electromagnetic compatibility
Limits for harmonic current emissions: conforming to IEC 61000-3-2
Conducted and radiated emissions: conforming to EN 55011 class B
Electrostatic discharge immunity test: class III, conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields: class III, conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: class III, conforming to IEC 61000-4-4
1.2/50 µs shock wave immunity test: class III, conforming to IEC 61000-4-5
Conducted RF disturbances: class III, conforming to IEC 61000-4-6
Immunity to impulse waves: class III, conforming to IEC 61000-4-8
Immunity to microbreaks and voltage drops: class III, conforming to IEC 61000-4-11
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage: conforming to IEC 61000-3-3
mounting mode
Flush-mounted
mounting support
Panel
type of installation
Indoor installation
overvoltage category
III
IP degree of protection
IP30 back: conforming to IEC 60529
IP52 front face: conforming to IEC 60529
relative humidity
95 % at 50 °C
pollution degree
2
ambient air temperature for operation
-5…50 °C
ambient air temperature for storage
-40…85 °C
operating altitude
0…3000 m
standards
IEC 61010-1
UL 508
CSA C22.2 No. 14
product certifications
CE
CULus
width
96 mm
depth
69 mm
height
96 mm
net weight
0.37 kg
Packing Units
Package 1: Weight
0.524 kg
Package 1: Height
1.600 dm
Package: 1 width
1.500 dm
Package 1 Length
1.600 dm
Offer Sustainability
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant
EU RoHS Declaration