Model:CM4250

Manufacturer :Schneider Electric

Square D

PowerLogic Circuit Monitor

100V-277V, 50VA, 50/60HZ

Schneider Electric Square D Powerlogic CM4250 Circuit Monitor

125V-250V 30W

CM4250

KYZ: 240V/300V   96mA MAX

CVM42

690V L-L/400V L-N MAX

5A NOM/10A MAX

 

Let us know your offer if the mentioned price is not good for you.

Main
range
PowerLogic.
product name
PowerLogic BCPM.
product or component type
Multi-circuit energy meter.
device’s short name
BCPMA.
Model type
Advanced.
power monitoring
Basic instrumentation.
energy management
Sub-billing and cost allocation.
device application
Sub billing.
power quality analysis
voltage sag and swell detection.
type of measurement
Voltage.
Current.
Frequency.
Active power.
Power factor.
Active energy.
[Us] rated supply voltage
90…277 V AC 50/60 Hz +/- 1%.
network frequency
60 Hz.
50 Hz.
Complementary
current transformer input
Solid-core CT 100 A42x.
update time
1.8 s
measurement voltage
90…277 V phase to neutral.
150…480 V, phase to phase.
measurement accuracy
Branch current: 2%, 0.25…2 A.
Branch current: 1%, 2… 100 A.
Mains current: 3%, 1%, 100%.
Mains current 3 % 2…100 %.
Voltage: 1 % 90…277 V
sampling rate
256 samples/cycle.
connection pitch
19 mm
provided equipment
42 x current transformer.
2 x cables.
communication port protocol
Modbus RTU.
communication port support
RS485.
communication of data
Low-current alarm.
High-current alarm.
Low-current alarm.
Under voltage alarm.
High-current alarm.
Over-voltage alarm.
Environment
mounting mode
Panel-mounted.
mounting support
Enclosure.
Panel.
relative humidity
0…95% at 0…60 °C.
ambient air temperature for storage
-40…70 °C.
operating altitude
3000 m
standards
IEC 61036.
ANSI C12.1.
UL 508.
EN 61010.
product certifications
UL.
width
288 mm.
height
146 mm.
net weight
1.5 kg.
Packing Units
Package 1: Weight
2500.000 g.
Package 1: Height
159.000 mm.
Package: 1 width
248.000 mm.
Package 1 Length
794.000 mm.
Offer Sustainability
REACh Regulation
REACh Declaration.
EU RoHS Directive
Compliant
EU RoHS Declaration.
Mercury free
Yes
RoHS exemption information
Yes
China’s RoHS Regulation
China RoHS declaration.
WEEE
The product must be disposed of on European Union markets following specific waste collection procedures and never end up in rubbish bins.
Contractual warranty
Warranty
18 months

The Schneider Electric CM4250 digital meter is an advanced and versatile tool designed for energy management, power quality monitoring, and data logging in industrial and commercial environments. This meter offers a comprehensive range of measurement capabilities, high accuracy, and robust communication features, making it an essential component for optimizing energy usage and ensuring the reliability of electrical systems.

Measurement Capabilities

The CM4250 provides extensive measurement capabilities, covering a wide range of electrical parameters:

  1. Voltage Measurement:
    • Measures phase-to-neutral and phase-to-phase voltages with an accuracy of ±0.2% of reading.
    • Voltage range: 0 to 600V (phase-to-phase) and 0 to 347V (phase-to-neutral).
  2. Current Measurement:
    • Measures current in each phase with an accuracy of ±0.2% of reading.
    • Current range: 0.1A to 10A (direct input), with the capability to measure higher ranges using external current transformers (CTs).
  3. Power Measurement:
    • Measures active, reactive, and apparent power with an accuracy of ±0.5% of reading.
    • Provides real-time power measurements to monitor and manage electrical loads effectively.
  4. Energy Measurement:
    • Measures energy consumption, including active and reactive energy, with an accuracy of ±0.5% of reading.
    • It helps in tracking energy usage over time for cost allocation and efficiency improvement.
  5. Frequency Measurement:
    • Monitors the frequency of the electrical supply with an accuracy of ±0.01 Hz.
    • Frequency range: 45 to 65 Hz.
  6. Harmonic Analysis:
    • Measures total harmonic distortion (THD) for voltage and current.
    • Provides analysis of individual harmonics up to the 50th order, helping to identify and address power quality issues.

Display and Interface

The CM4250 features a user-friendly display and interface designed for ease of use and clear visibility.

  • LCD/LED Display:
    • Large, backlit display for easy reading of multiple parameters simultaneously.
    • A high-resolution display ensures precise reading of values.
  • User Interface:
    • Equipped with buttons or a touch screen for navigation through menus and settings.
    • Intuitive menu structure for quick access to measurement data and configuration options.