Description
range of product | Modicon Premium Automation platform. |
---|---|
product or component type | Unity processor. |
software designation | Unity Pro. |
concept | Transparent Ready. |
---|---|
number of racks | 16 4/6/8 slots. 8-12 slots. |
number of slots | 128 64 96 |
discrete I/O processor capacity | 1024 I/O |
analogue I/O processor capacity | 128 I/O |
number of application-specific channel | 32 |
number of process control channel | 15 up to 45 simple loops. |
integrated connection type | Non isolated serial link 2 female mini DIN. connector (RS485) (19.2/115-kbit/s). Ethernet TCP/IP RJ45 connector. |
port Ethernet | 10BASE-T/100BASE-TX. |
communication module processor capacity | 2 1 3 8 |
memory description | Internal RAM (with PCMCIA card): 1792 kB. program. Internal RAM (with PCMCIA card): 192 kB data. Internal RAM (without PCMCIA card) 192 kB. program and data. PCMCIA card: 16384 kB of additional data storage. |
maximum size of object areas | 16384 %Mi located internal bits. 64 % KWi constant words located internal data. 64 percent of internal words located internal data. 64 kB (DFB and EFB function blocks) unlocated. internal data. 64 kB (elementary and derived data) unlocated internal data. |
application structure | 1 master task. 1 fast task. 64 event tasks. |
execution time per instruction | 0.12 µs Boolean without PCMCIA card. 0.17 µs Boolean with PCMCIA card. 0.17 µs word or fixed-point arithmetic without a PCMCIA card. 0.32 µs word or fixed-point arithmetic with a PCMCIA card. 1.75…3 µs floating points with PCMCIA card. 1.75…3 µs floating points without a PCMCIA card. |
number of instructions per ms | 3.11 Kinst/ms: 65 % Boolean + 35 % fixed arithmetic with PCMCIA card. 4.59 Kinst/ms 100 % Boolean with PCMCIA card 5.11 Kinst/ms: 65 % Boolean + 35 % fixed. arithmetic without PCMCIA card. 6.72 Kinst/ms 100 % Boolean without PCMCIA card. |
system overhead | 0.35 ms for fast task. 1 ms for master task. |
marking | CE |
local signalling | 1 LED (green) for Ethernet TCP/IP port readiness. (RUN). 1 LED (green) for processor running (RUN). 1 LED (red) for collision detection (COL). 1 LED (red) for Ethernet TCP/IP port fault (ERR). 1 LED (red) for the I/O module or configuration fault (I/O). 1 LED (red) for processor or system fault (ERR). 1 LED (yellow) for activity on TER or AUX. terminal port (TER). 1 LED (yellow) for Ethernet link diagnostics (STS) 1 LED (yellow) for reception activity (RX). 1 LED (yellow) for transmission activity (TX). |
current consumption | 1900 mA at 5 V DC. |
module format | Double |
net weight | 0.64 kg |
standards | CSA C22.2 No. 213 Class I Division 2 Group D. CSA C22.2 No. 142. CSA C22.2 No. 213 Class I Division 2 Group C. UL 508. 93/68/EEC. CSA C22.2 No. 213 Class I Division 2 Group B. CSA C22.2 No. 213 Class I Division 2 Group A 89/336/EEC. IEC 61131-2. 92/31/EEC 73/23/EEC. |
---|---|
product certifications | LR RINA RMRS ABS GL BV DNV |
ambient air temperature for operation | 0…60 °C |
ambient air temperature for storage | -25…70 °C |
relative humidity | 10…95 % without condensation for operation. 5…95 % without condensation for storage. |
operating altitude | 0…2000 m. |
protective treatment | TC |
IP degree of protection | IP20 |
pollution degree | 2 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1: Weight | 757.0 g |
Package 1: Height | 9.5 cm |
Package: 1 width | 18.0 cm |
Package 1 Length | 26.0 cm |
Unit Type of Package 2 | S04 |
Number of Units in Package 2 | 6 |
Package 2: Weight | 5.489 kg |
Package 2: Height | 30.0 cm |
Package 2 width | 40.0 cm |
Package 2 Length | 60.0 cm |
Detailed Explanation:
1. PLC Overview:
- Model TSXP573634M is part of the Modicon TSX Premium series, known for its robust performance and reliability in industrial automation applications.
- Purpose: It serves as a central control unit in automated systems, executing logic functions based on programmed instructions to monitor and control machinery and processes.
2. Key Features:
- Processing Power: Equipped with a powerful processor capable of handling complex control tasks and real-time operations in industrial environments.
- Memory: Offers sufficient memory capacity for storing program logic, data tables, and configuration parameters, ensuring efficient operation and flexibility in application development.
- I/O Interfaces: Provides multiple input and output interfaces to connect sensors, actuators, and other devices, supporting various industrial communication protocols for seamless integration.