Range of product | Modicon Quantum automation platform. |
---|---|
Product or component type | Intrinsically safe temperature input module. |
Software designation | Concept version V2.2 and above Unity Pro. |
Type of filter | Plus-notch input filter, 50/60 Hz thermocouple. Single low-pass input filter, 20 Hz thermocouple. |
Product destination | In conjunction with products for zone 20, 21 or 22, |
---|---|
Analogue input number | 8 |
Analogue input type | Low level voltage: -100…100 mV. Low level voltage: -25…25 mV. Thermocouple: 210–760 °C for thermocouple J. Thermocouple: 270–1000 °C for thermocouple. E. Thermocouple: 270–1370 °C for thermocouple K. Thermocouple: 270–400 °C for thermocouple T. Thermocouple: 50–1665 °C for thermocouple R. Thermocouple: 50–1665 °C for thermocouple S. Temperature probe: 200–850 °C for Pt 100, Pt 200, Pt 500, and Pt 1000. Temperature probe: 60–180 °C for Ni 100, Ni 200, Ni 500, and Ni 1000. Thermocouple: 130–1820 ° C for thermocouple B. |
Measurement current | 0.5 mA Pt 500, Pt 1000, Ni 500, Ni 1000. 2.5 mA Pt 100, Pt 200, Ni 100, Ni 200. |
Source resistance | < 200 Ohm thermocouple. |
Input impedance | > 10 MOhm RTD. thermocouple. |
Common mode rejection | > 100 dB 50/60 Hz RTD. > 120 dB 50/60 Hz thermocouple. |
Cold junction compensation | Internal 0…60 °C thermocouple. |
Linearity | 0.003 % of full-scale RTD. |
Resolution | 0.76 µV (16 bits) -25…25 mV millivolt. 3.05 µV (16 bits) -100…100 mV millivolt. 1 °C, 0.1 °C, 1 °F, 0.1 °F thermocouple. 12 bits + sign (0.1 °C) RTD. |
Measurement accuracy | +/- 2 °C + 0.1 % of reading thermocouple E. +/- 2 °C + 0.1 % of reading thermocouple J. +/- 2 °C + 0.1 % of reading thermocouple K. +/- 2 °C + 0.1 % of reading thermocouple T. +/- 4 °C + 0.1 % of reading thermocouple B. +/- 4 °C + 0.1 % of reading thermocouple R. +/- 4 °C + 0.1 % of reading thermocouple S. +/- 0.5 °C RTD at 25 °C. +/- 0.9 °C RTD at 0…60 °C. 20 µV + 0.1 % of reading millivolt at 25 °C. |
Absolute accuracy error | +/- 0.05 % of full-scale RTD at 25 °C. +/- 0.1 % of full-scale maximum RTD at 25 °C. |
Accuracy drifts according to temperature | 0.15 mV/°C + 0.0015 % of reading/°C max thermocouple. |
Update time | 1 s TC/millivolt thermocouple. 1.35 s 3 wires RTD. 750 ms 2 or 4 wire RTD. |
Isolation between channels and bus | 1780 V, 47.63 Hz AC for 1 minute. 2500 V DC for 1 minute. |
Fault type | Broken wire. Out of range. |
Power dissipation in W | 2 W. |
Hot swapping fallback | Not allowed per intrinsic safety standards. |
Protection type | Internal fuse. |
marking | CE II1 G/D-EEx ia IIC. |
The current bus requirement | 400 mA. |
Module format | Standard. |
Product weight | 0.3 kg |
standards | EN 50281-1-1. EN 50014. EN 50284 CSA C22.2 No. 142. EN 50020 Directive ATEX 94/9/EC. EN 50039. |
---|---|
Dust zone | Outside zone. |
Product certifications | Hazardous location class 1, division 1 groups A, B, and C. C-Tick.1. FM Class 1 Division 2. SIRA 02ATEX2345X. |
Resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2. 8 kV on air, conforming to IEC 801-2. |
Resistance to electromagnetic fields | 10 V/m 80…2000 Hz, conforming to IEC 801-3. |
Ambient air temperature for operation | 0…60 °C. |
Ambient air temperature for storage | -40…85 °C. |
Relative humidity | 95 % without condensation. |
Operating altitude | <= 5000 m. |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1: Height | 4.5 cm. |
Package 1: Width | 16.5 cm. |
Package 1 Length | 31.5 cm.. |
Package 1: Weight | 0.676 kg. |