Description
Description
Analog Output Module Modicon Quantum – 4 O
range of product | Modicon Quantum automation platform | |
---|---|---|
product or component type | Analogue output module |
analogue output number | 4 | |
---|---|---|
addressing requirement | 4 output words | |
analogue output range | +/- 10 V >= 1000 Ohm bipolar voltage +/- 5 V >= 500 Ohm bipolar voltage 0…10 V >= 1000 Ohm unipolar voltage 0…5 V >= 500 Ohm unipolar voltage | |
analogue output resolution | 12 bits | |
analogue output current | -10…10 mA | |
source resistance | 0.1 Ohm | |
cable distance between devices | 400 m | |
absolute accuracy error | +/- 0.15 % of full scale at 77 °F (25 °C) | |
linearity | +/- 1 LSB | |
accuracy drift according to temperature | 0.003 % of full scale/°C unipolar 0.004 % of full scale/°C bipolar 0.005 % of full scale/°C maximum unipolar 0.007 % of full scale/°C maximum bipolar | |
isolation between channels | 500 V for 1 minute 47…63 Hz AC | |
isolation between channels and bus | 780 V for 1 minute AC | |
update time | 3 ms | |
setting time | 700 µs to +/- 0.1 % of the final value maximum | |
bus current requirement | 700 mA | |
power dissipation in W | <= 4.5 W | |
associated fuse rating | 0.063 mA 3 AG fast blow 250 V | |
marking | CE | |
local signalling | 4 LEDs green channel is turned on 4 LEDs red channel fault 1 LED green bus communication is present (Active) 1 LED red external fault | |
module format | Standard | |
product weight | 0.66 lb(US) (0.3 kg) |
product certifications | CUL FM Class 1 Division 2 | |
---|---|---|
standards | UL 508 CSA C22.2 No 142 | |
resistance to electromagnetic fields | 9.14 V/yd (10 V/m) 80…2000 MHz conforming to IEC 801-3 | |
ambient air temperature for operation | 32…140 °F (0…60 °C) | |
ambient air temperature for storage | -40…185 °F (-40…85 °C) | |
relative humidity | 95 % without condensation | |
operating altitude | <= 16404.2 ft (5000 m) |