Distributed analog input Modicon Momentum 170AAI03000, 8 Input
range of product |
Modicon Momentum is an automation platform.
|
|
---|---|---|
product or component type |
Analogue input base
|
|
analogue input number |
8
|
|
analogue input type |
Differential
|
|
analogue input range |
+/- 20 mA, 14 bits, +/- 250 kOhm.
4…20 mA, 15 bits + sign, 250 kOhm. +/- 10 V, 14 bits + sign > 0.1 kOhm. +/- 5 V, 14 bits + sign > 0.1 kOhm. 1…5 V, 15 bits + sign > 0.1 kOhm. |
data format |
Full 16 bits signed
|
|
---|---|---|
absolute accuracy error |
+/- 0.13 % full scale 25 °C 1…5 V.
+/- 0.19 % full scale 60 °C 1…5 V. +/- 0.21 % full scale 25 °C +/- 5 V. +/- 0.26 % full scale 60 °C +/- 5 V. +/- 0.27 % full scale 25 °C +/- 10 V. +/- 0.27 % full scale 25 °C, 4…20 mA. +/- 0.32 % full scale, 25 °C +/- 20 mA. +/- 0.32 % full scale 60 °C +/- 10 V. +/- 0.38 % full scale, 60 °C, 4…20 mA. +/- 0.41 % full scale, 60 °C +/- 20 mA. |
|
conversion time |
12 ms. 8
|
|
isolation between channels |
+/- 200 V DC for 1 minute.
|
|
isolation between channels and ground |
500 V AC for 1 minute.
|
|
isolation between channels and bus |
500 V AC for 1 minute.
|
|
permissible common-mode voltage |
100 V, 47…63 Hz DC between channels to ground.
250 V 47…63 Hz AC between channels to ground. |
|
common mode rejection |
> 80 dB between channels and ground.
|
|
external power requirement |
< 382 mA DC.
20.4…28.8 V DC 24 V DC. |
|
reverse-polarity protection |
Internal
|
|
marking |
CE
|
|
local signalling |
1 LED (green) is ready.
8 LEDs for channel status. |
|
electrical connection |
2 connectors for removable terminal blocks.
|
|
depth |
47.5 mm
|
|
height |
125 mm
|
|
width |
141.5 mm
|
|
net weight |
0.215 kg
|
standards |
EN 50081-2
IEC 1131 |
|
---|---|---|
product certifications |
FM Class 1 Division 2
CSA UL |
|
protective treatment |
TC
|
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2.
8 kV on air, conforming to IEC 801-2. |
|
resistance to electromagnetic fields |
10 V/m 80…1000 MHz, conforming to IEC 801-3.
|
|
ambient air temperature for operation |
0…60 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
|
relative humidity |
95% without condensation.
|
|
operating altitude |
<= 5000 m
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Number of Units in Package 1 |
1
|
|
Package 1: Weight |
398 g
|
|
Package 1: Height |
5.5 cm
|
|
Package: 1 width |
18 cm
|
|
Package 1 Length |
26 cm
|
Sustainable offer status |
Green premium product.
|
|
---|---|---|
REACh Regulation |
REACh Declaration.
|
|
EU RoHS Directive |
Pro-active compliance (products outside of the EU RoHS legal scope).
EU RoHS Declaration. |
|
Mercury free |
Yes
|
|
RoHS exemption information |
Yes
|
|
China’s RoHS Regulation |
China RoHS declaration.
|
|
Environmental Disclosure |
Product Environmental Profile.
|
|
Circularity Profile |
End-of-life information.
|
|
WEEE |
The product must be disposed of on European Union markets following specific waste collection procedures and never end up in rubbish bins.
|
The Modicon 170AAI03000 is an analog input module used in the Modicon automation platform, which is part of Schneider Electric’s range of programmable logic controllers (PLCs). This module is designed to interface with analog sensors and devices, converting their signals into digital data that can be processed by the PLC.
Key Features:
- Analog Inputs:
- The 170AAI03000 module provides multiple analog input channels. Each channel can receive signals from various types of analog sensors, such as temperature sensors, pressure transducers, and flow meters.
- Signal Types:
- The module supports a range of input signal types, typically including voltage (e.g., 0–10V) and current (e.g., 4–20 mA). This versatility allows it to be used with a wide variety of analog devices.
- Resolution and Accuracy:
- High-resolution analog-to-digital conversion ensures accurate representation of the input signals. This precision is crucial for applications where exact measurements are necessary.
- Isolation:
- The inputs are often isolated from the control logic to protect the PLC and ensure reliable operation, even in electrically noisy environments.
- Diagnostics and Indicators:
- Built-in diagnostic features and LED indicators provide status information and help troubleshoot any issues with the inputs.