Description

Main
rangePowerLogic
product namePowerLogic PM5000
device’s short namePM5310
product or component typePower meter
Complementary
power quality analysisUp to the 31st harmonic
device applicationMulti-tariff
Power monitoring.
type of measurementCurrent
Voltage.
Frequency.
Power factor
Energy.
Active and reactive power.
supply voltage100…415 V AC 45…65 Hz
125–250 V DC.
network frequency50 Hz
60 Hz.
[In] rated current1 A
5 A
type of network1P + N.
3P
3P + N.
maximum power consumption in VA10 VA at 415 V
ride-through time80 ms. 120 V AC is typical.
100 ms 230 V AC, typical.
100 ms 415 V AC, typical.
display typeBacklit LCD.
display resolution128 x 128 pixels
sampling rate64 samples/cycle.
measurement current10…9000 mA
analogue input typeVoltage (impedance: 5 MOhm).
Current (impedance 0.3 mOhm).
measurement voltage35–690 V AC, 45–65 Hz between phases.
20–400 V AC, 45–65 Hz between phase and neutral.
frequency measurement range45…65 Hz.
number of inputs2 digital
measurement accuracyActive energy +/- 0.5%.
Reactive energy +/- 2%.
Active power +/- 0.5%.
Apparent power +/- 0.5%.
Frequency +/- 0.05%.
Power factor +/- 0.005.
Current +/- 0.5%.
Voltage +/- 0.5%.
accuracy classClass 0.5S active energy conforms to IEC 62053-22.
number of outputs2 digital.
information displayedTariff (4).
communication port protocolModbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds, even/odd or none. 2 wires, insulation, 2500 V
JBUS.
communication port supportRS485
data recordingEvent logs
Min/max of instantaneous values.
Alarm logs.
Data logs.
Time stamping
Maintenance logs.
memory capacity256 kB
connections—terminalsVoltage circuit: screw terminal block 4.
Control circuit: screw terminal block 2.
Current transformer: screw terminal block 6.
Input/output circuit: screw terminal block 6.
Relay output: screw terminal block 4.
Ethernet network: RJ45 connector.
mounting modeFlush-mounted.
mounting supportFramework
standardsEN 50470-3.
IEC 62053-24.
IEC 60529.
EN 50470-1.
UL 61010-1.
IEC 62053-22.
IEC 61557-12.
product certificationsCE conforming to IEC 61010-1.
CULus conforms to UL 61010-1.
width96 mm.
depth72 mm.
height96 mm.
net weight430 g