RM4TR32 – three-phase network control relay RM4-T
Original price was: $444.00.$342.00Current price is: $342.00.
The RM4TR32 is a versatile three-phase network control relay from Schneider Electric designed to monitor and protect three-phase electrical systems.
7 in stock
Free shipping on orders over $5000!
- Satisfaction Guaranteed
- No Hassle Refunds
- Secure Payments
Description
| range of product |
Harmony Relay RM4TR32.
|
|
|---|---|---|
| product or component type |
Industrial measurement and control relays.
|
|
| relay type |
Control relay.
|
|
| product-specific application | ||
| relay name |
RM4-T.
|
|
| relay monitored parameters |
Phase failure detection.
Phase sequence. Overvoltage and undervoltage detection. |
|
| time delay |
Adjustable 0.1…10 s.
|
|
| measurement range |
290…484 V.
|
|
| contacts type and composition |
2 C/O.
|
|
| poles description |
3P.
|
| maximum switching voltage |
440 V AC.
|
|
|---|---|---|
| control threshold undervoltage |
300…430 V.
|
|
| control threshold overvoltage |
420…480 V.
|
|
| output contacts |
2 C/O.
|
|
| setting accuracy of the switching threshold |
+/-3 %.
|
|
| switching threshold drift |
<= 0.06 % per degree centigrade, depending. permissible ambient air temperature.
<= 0.5 % within the measuring range. |
|
| setting accuracy of time delay |
10 P.
|
|
| time delay drift |
<= 0.07 % per degree Celsius, depending on. the rated operational temperature.
<= 0.5 % within the measuring range. |
|
| hysteresis |
5 % fixed of de-energization threshold.
|
|
| delay at power up |
650 ms.
|
|
| maximum measuring cycle |
80 ms
|
|
| marking |
CE.
|
|
| overvoltage category |
III, conforming to IEC 60664-1.
|
|
| [Ui] rated insulation voltage |
500 V, conforming to the IEC.
|
|
| supply frequency |
50/60 Hz +/- 5%.
|
|
| operating position |
Any position without derating.
|
|
| connections—terminals |
Screw terminals, 2 x 1.5 mm flexible with cable end.
Screw terminals, 2 x 2.5 mm flexible without cable ends. |
|
| tightening torque |
0.6…1.1 N.m.
|
|
| mechanical durability |
30000000 cycles.
|
|
| conventional free-air thermal current |
8 A.
|
|
| [Ie] rated operational current |
2 A at 70 °C, 24 V DC-13, conforming to IEC 60947-5-1/1991.
2 A at 70 °C, 24 V DC-13, conforming to VDE 0660. 3 A at 70 °C, 115 V AC-15, conforming to IEC. 60947-5-1/1991. 3 A at 70 °C, 115 V AC-15, conforming to VDE 0660. 3 A at 70 °C, 24 V AC-15, conforming to IEC 60947-5-1/1991. 3 A at 70 °C, 24 V AC-15, conforming to VDE 0660. 3 A at 70 °C 250 V AC-15 conforming to IEC. 60947-5-1/1991. 3 A at 70 °C 250 V AC-15 conforming to VDE. 0660. 0.1 A at 70 °C 250 V DC-13 conforming to IEC. 60947-5-1/1991. 0.1 A at 70 °C 250 V DC-13 conforming to VDE 0660. 0.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/1991. 0.3 A at 70 °C 115 V DC-13 conforming to VDE 0660. |
|
| switching capacity in mA |
10 mA at 12 V.
|
|
| switching voltage |
250 V AC.
|
|
| contacts material |
90/10 silver nickel contacts.
|
|
| number of cables |
2
|
|
| height |
78 mm.
|
|
| width |
22.5 mm.
|
|
| depth |
80 mm.
|
|
| terminals description: ISO n°1 |
(15-16-18)OC.
(L1-L2-L3)CO. (25-26-28)OC. |
|
| output relay state |
Tripped, fault present.
|
|
| 9 mm pitches |
2.5.
|
|
| net weight |
0.11 kg.
|
| electromagnetic compatibility |
Electrostatic discharge – test level: 6 kV level 3. (contact discharge) conforming to IEC 61000-4-2.
Electrostatic discharge – test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2. Resistance to electrostatic discharge – test level: 6 kV (contact) conforming to IEC 61000-4-2 level 3. Resistance to electrostatic discharge – test level: 8. kV (air) conforming to IEC 61000-4-2 level 3. |
|
|---|---|---|
| standards |
EN/IEC 60255-6.
|
|
| product certifications |
CSA
GL. UL |
|
| directives |
73/23/EEC – low voltage directive.
89/336/EEC – electromagnetic compatibility. |
|
| ambient air temperature for storage |
-40…85 °C
|
|
| ambient air temperature for operation |
-20…65 °C.
|
|
| relative humidity |
15…85 % 3K3 conforming to IEC 60721-3-3.
|
|
| vibration resistance |
0.35 ms (f= 10…55 Hz) conforming to IEC 60068-2-6.
|
|
| shock resistance |
15 gn for 11 ms, conforming to IEC 60068-2-27.
|
|
| IP degree of protection |
IP20 (terminals) conforming to IEC 60529.
IP50 (casing) conforming to IEC 60529. |
|
| pollution degree |
conforming to IEC 60664-1.
|
|
| dielectric test voltage |
2.5 kV
|
|
| non-dissipating shock wave |
4.8 kV
|
|
| resistance to electrostatic discharge |
6 kV contact conforming to IEC 61000-4-2 level 3.
8 kV air conforming to IEC 61000-4-2 level 3. |
|
| resistance to electromagnetic fields |
10 V/m conforming to IEC 61000-4-3 level 3.
|
|
| resistance to fast transients |
2 kV, conforming to IEC 61000-4-4 level 3.
|
|
| disturbance radiated/conducted |
CISPR 11 group 1 – class A.
CISPR 22: Class A. |