Main
range of product PowerLogic PM700.
device short name PM750.
product or component type Power meter.
Complementary
power quality analysis Total harmonic distortion.
type of measurement Current.
Voltage.
Frequency.
Power factor total..
Apparent power total.
Active power total.
Reactive power total.
Apparent power per phase.
Active power per phase.
Reactive power per phase.
Energy.
supply voltage 125…250 V DC.
115…415 V AC 45…65 Hz.
network frequency 45…65 Hz.
maximum power consumption in VA 5 VA
display type Backlit LCD.
display resolution 6 lines.
sampling rate 32 samples/cycle.
measurement current 5 A.
1 A.
input type Current: 0.005…6 A (impedance <= 0.1 Ohm).
measurement voltage 10…480 V AC 45…65 Hz, phase to phase.
10…277 V AC 45…65 Hz phase to neutral.
number of inputs 2 digital.
measurement accuracy Frequency: 0.02 Hz, 45–65 Hz.
Power factor: 0.0034, 1A to 6A, and from -0.5 to +0.5.
Current 0.4% 1…6 A.
Voltage: 0.3%, 50–227 V.
Power: 0.5%.
accuracy class Class 2 reactive energy conforms to IEC 62053-23.
Class 0.5S active energy conforms to IEC 62053-22.
Class 0.5 active energy conforms to ANSI C12.20.
number of outputs 1 digital (static).
communication port protocol Modbus 19.2 kbauds.
communication port support RS485.
data recording Alarms
Min/max of instantaneous values.
Environment
electromagnetic compatibility Limits for harmonic current emissions: conforming to IEC 61000-3-2.
Conducted and radiated emissions, conforming to EN 55011 class B.
Electrostatic discharge immunity test: class III, conforming to IEC 61000-4-2.
Susceptibility to electromagnetic fields: class III, conforming to IEC 61000-4-3.
Electrical fast transient/burst immunity test: class III, conforming to IEC 61000-4-4.
1.2/50 µs shock wave immunity test: class III, conforming to IEC 61000-4-5.
Conducted RF disturbances, class III, conforming to IEC 61000-4-6.
Immunity to impulse waves: class III, conforming to IEC 61000-4-8.
Immunity to microbreaks and voltage drops: class III, conforming to IEC 61000-4-11.
Limitation of voltage changes, voltage fluctuations, and flicker in low-voltage: conforming to IEC 61000-3-3.
mounting mode Flush-mounted.
mounting support Panel.
type of installation Indoor installation.
overvoltage category III
IP degree of protection IP30 back: conforming to IEC 60529.
IP52 front face: conforming to IEC 60529.
relative humidity 95 % at 50 °C.
pollution degree 2
ambient air temperature for operation -5…50 °C.
ambient air temperature for storage -40…85 °C.
operating altitude 0…3000 m.
standards IEC 61010-1.
CSA C22.2 No. 14.
UL 508.
product certifications CE.
cULus.
width 96 mm.
depth 69 mm.
height 96 mm.
net weight 0.37 kg.