Sale!

BMXDRA0805 Modicon X80

Original price was: $166.00.Current price is: $128.00.

2 in stock

Category:

Description

Main
range of productModicon X80
product or component typeDiscrete output module.
discrete output number8 conforming to EN/IEC 61131-2.
discrete output typeRelay
discrete output voltage24…240 V 19…264 V AC
12…24 V 10…34 V DC.
Complementary
conventional free-air thermal current3 A
insulation resistance> 10 MOhm, 500 V DC
power dissipation in W2.7 W
response time on output< 10 ms activation
< 8 ms deactivation.
typical current consumption79 mA at 3.3 V DC
MTBF reliability2119902 H
output overload protectionUse 1 fast-blow fuse per channel or group of channel.
output overvoltage protectionUse discharge diode on each output DC
Use RC circuit on each output AC.
Use a ZNO surge limiter on each output AC.
output short-circuit protectionUse 1 fast-blow fuse per channel or group of channels.
minimum switching current10 mA, 5 V DC
electrical durabilityAC-15: 100000 cycles at 220 VA, 200…240 V (load factor 0.35).
AC-12: 1000000 cycles at 110 VA, 110…120 V.
AC-12: 1000000 cycles at 220 VA, 200…240 V.
AC-12: 1000000 cycles at 50 VA, 48 V.
AC-15: 1000000 cycles at 110 VA 200 VA, and 240 VA. (load factor 0.35).
DC-12: 1000000 cycles at 24 W, 24 V.
DC-13: 1000000 cycles at 24 W, 24 V.
AC-15: 10000000 cycles at 10 VA, 110–120 V. (load factor 0.35).
AC-15: 10000000 cycles at 10 VA, 200…240 V (load factor 0.35).
AC-15: 150000 cycles at 110 VA, 110…120 V (load factor 0.35).
AC-15: 1500000 cycles at 50 VA 110 VA, and 120 VA (load factor 0.35).
AC-15: 2000000 cycles at 24 VA, 48 V (load factor 0.35).
DC-13: 2000000 cycles at 10 W and 24 V
DC-12: 300000 cycles at 40 W and 24 V.
AC-15: 3000000 cycles at 50 VA, 200…240 V (load factor 0.35).
AC-12: 500000 cycles at 110 VA, 48 V.
AC-12: 500000 cycles at 220 VA, 110–120 V.
AC-15: 5000000 cycles at 10 VA, 48 V (load factor 0.35).
AC-15: 500000 cycles at 24 VA/24 V (load factor 0.35).
AC-12: 700000 cycles at 50 VA, 24 V.
status LED1 LED (green) module operating (RUN).
1 LED per channel (green) is diagnostic.
1 LED (red) module error (ERR).
1 LED (red) module I/O.
net weight0.145 kg
Environment
IP degree of protectionIP20
directives2014/35/EU: Low Voltage Directive
2014/30/EU: electromagnetic compatibility.
environmental characteristicCorrosion resistance
Dust resistant.
dielectric strength2000 V AC at 50/60 Hz, 1 min
vibration resistance3 gn.
shock resistance30 gn.
ambient air temperature for storage-40…85 °C.
ambient air temperature for operation0…60 °C.
relative humidity5…95%% at 55 °C without condensation.
operating altitude0…2000 m
2000–5000 m with a derating factor.
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1: Weight177.0 g
Package 1: Height5.5 cm
Package: 1 width11.0 cm
Package 1 Length12.0 cm
Unit Type of Package 2S02
Number of Units in Package 215
Package 2: Weight2.911 kg
Package 2: Height15.0 cm
Package 2 width30.0 cm
Package 2 Length40.0 cm