Description
Specifications
Range | PowerLogic |
---|---|
Device short name | ION6200 |
Product or component type | Energy and power quality meter |
Power quality analysis | harmonic distortion |
---|---|
Device application | Metering |
Type of measurement | Active and reactive energy Apparent energy Current Voltage Frequency Harmonic distorsion (I THD & U THD) Active and reactive power total Apparent power total Power factor Demand current (I1, I2, I3, Ig) Active and reactive power per phase Apparent power per phase |
supply voltage | 100…240 V AC 50/60 Hz 110…300 V DC |
Network frequency | 60 Hz 50 Hz |
[In] rated current | 10 A |
type of network | 3P + N 3P 2P + N |
Power consumption in VA | 0.05 VA |
Display type | 7 segments LED + decimal point |
Sampling rate | 64 samples/cycle |
Measurement current | 0.005…12 A |
Measurement voltage | 60…400 V AC 50…60 Hz between phase and neutral 103.5…690 V AC 50…60 Hz between phases |
Frequency measurement range | 50…60 Hz |
Number of inputs | 0 |
Measurement accuracy | Current 0.3 % Voltage 0.3 % Power +/- 0.5 % Frequency +/- 0.1 % Power factor +/- 1 % Energy +/- 0.5 % |
Accuracy class | Class 0.5 power conforming to IEC 60687 Class 0.5 energy conforming to IEC 60687 Class 0.5 power conforming to ANSI C12.20 Class 0.5 energy conforming to ANSI C12.20 |
Number of outputs | 2 pulse |
Communication port protocol | Modbus RTU, master at 19200 bauds ION |
Communication port support | Screw terminal block: RS485 isolated |
Transmission rate | 19200 bauds |
Tamperproof of settings | Protected by access code |
Electromagnetic compatibility | Electrostatic discharge immunity test conforming to IEC 61000-4-2 Immunity to radiated fields conforming to IEC 61000-4-3 Immunity to fast transients conforming to IEC 61000-4-4 Surge immunity test conforming to IEC 61000-4-5 Conducted radio-frequency immunity test conforming to IEC 61000-4-6 Emission standard for industrial environments conforming to IEC 61000-4-2 |
---|---|
mounting mode | Panel-mounted |
Mounting support | Enclosure door |
Type of installation | Indoor installation |
IP degree of protection | IP30 back: IP65 front: |
Relative humidity | 5…95 % |
Pollution degree | 2 |
Ambient air temperature for operation | -20…70 °C |
Ambient air temperature for storage | -40…85 °C |
Product certifications | CUL conforming to CSA C22.2 |
Standards | CSA 1010-1 EN 61010-1 UL 3111-1 |
Width | 110 mm |
Depth | 65 mm |
Height | 110 mm |
Net weight | 0.68 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |