Sale!

METSEPM5100 – PM5100 Meter, without communication

Original price was: $211.00.Current price is: $162.00.

Schneider Electric’s METSEPM5100 PM5100 Meter is designed for straightforward power and energy monitoring without the need for communication features.

4 in stock

Category:

Description

Main
range PowerLogic.
product name PowerLogic PM5000.
device short name PM5100.
product or component type Power meter.
Complementary
power quality analysis Up to the 15th harmonic.
device application Power monitoring.
type of measurement Current.
Voltage.
Frequency.
Power factor.
Energy.
Active and reactive power.
supply voltage 100…415 V AC 45…65 Hz.
125…250 V DC.
network frequency 60 Hz.
50 Hz.
[In] rated current 5 A.
1 A.
type of network 3P + N..
1P + N.
3P..
maximum power consumption in VA 10 VA at 415 V
ride-through time 80 ms/120 V AC is typical.
100 ms, 230 V AC is typical.
100 ms, 415 V AC is typical.
display type Backlit LCD.
display resolution 128 x 128 pixels.
sampling rate 64 samples/cycle.
measurement current 10…9000 mA.
analogue input type Voltage (impedance: 5 MOhm).
Current (impedance 0.3 mOhm).
measurement voltage 35…690 V AC, 45…65 Hz between phases.
20…400 V AC, 45…65 Hz between phase and neutral.
frequency measurement range 45…65 Hz.
number of inputs 0
measurement accuracy Active energy +/- 0.5%.
Reactive energy +/- 2%.
Active power +/- 0.5%.
Apparent power +/- 0.5%.
Frequency +/- 0.05%.
Power factor +/- 0.005.
Current +/- 0.5%.
Voltage +/- 0.5%.
accuracy class Class 0.5S active energy conforming to IEC. 62053-22.
number of outputs 1 digital.
communication port protocol
communication port support
data recording Min/max of instantaneous values
Time stamping.
connections – terminals Voltage circuit: screw terminal block 4.
Control circuit: screw terminal block 2.
Current transformer: screw terminal block 6.
Input/output circuit: screw terminal block 6.
RS485 link: screw terminal block 4.
mounting mode Flush-mounted.
mounting support Framework.
standards EN 50470-1.
IEC 62053-22.
UL 61010-1.
IEC 62053-24.
IEC 61557-12.
EN 50470-3.
IEC 60529.
product certifications CE conforming to IEC 61010-1.
CULus conforms to UL 61010-1.
width 96 mm.
depth 72 mm.
height 96 mm
net weight 380 g.
Environment
electromagnetic compatibility Limits for harmonic current emissions in class A conforming to IEC 61000-3-2.
Electrostatic discharge level 4 conforms to IEC 61000-4-2.
Conducted RF disturbances at level 3, conforming to IEC 61000-4-6.
Magnetic field at power frequency level 4 conforms to IEC 61000-4-8.
Conducted and radiated emissions in class B, conforming to EN 55022.
IP degree of protection IP52 front: conforming to IEC 60529.
IP30 body: conforming to IEC 60529.
relative humidity 5% at 50 °C.
pollution degree 2
ambient air temperature for operation -25…70 °C.
ambient air temperature for storage -40…85 °C.
operating altitude 3000 m.
Packing Units
Unit Type of Package 1 PCE.
Package 1 Length 12.6 cm.
Number of Units in Package 1 1
Package 3 Width 80.0 cm.
Package 3 Weight 61.44 kg.
Package 2 Width 30.0 cm.
Package 2 Height 30.0 cm.
Package 2 Weight 6.54 kg.
Number of Units in Package 3 96.
Unit Type of Package 3 P06.
Package 3 Height 50.0 cm.
Package 3 Length 60.0 cm.
Package 1 Width 12.6 cm.
Package 1 Height 11.0 cm.
Package 1 Weight 550.0 g.
Number of Units in Package 2 12.
Unit Type of Package 2 S03.
Package 2 Length 40.0 cm.

The METSEPM5100, part of Schneider Electric’s PowerLogic PM5000 series, is a versatile power meter designed to provide accurate and reliable monitoring of electrical systems. Unlike some advanced meters that offer extensive communication capabilities, the PM5100 focuses on delivering essential measurement functions without communication features. This makes it an ideal choice for applications where straightforward, reliable power and energy monitoring is required without the complexity of network integration.

Key Features and Specifications

High-Accuracy Measurements

The METSEPM5100 delivers precise measurement capabilities, ensuring high accuracy for critical electrical parameters:

  • Voltage and Current Measurement: The meter provides accurate readings of voltage and current, which are fundamental for monitoring electrical system performance.
  • Power and Energy Measurement: It measures active, reactive, and apparent power, as well as energy consumption, aiding in effective energy management and cost control.
  • Power Factor: Monitoring power factor helps in identifying inefficiencies in the system and taking corrective actions to improve energy usage.

User-Friendly Interface

The PM5100 is designed with ease of use in mind, featuring:

  • Clear Display: The meter comes with a clear, easy-to-read display that presents data in a straightforward manner, allowing users to quickly understand the status of their electrical systems.
  • Intuitive Navigation: The interface is designed for simple navigation, making it easy to access and review different parameters and historical data.

Compact and Robust Design

  • Durable Construction: Built to withstand the demands of industrial and commercial environments, the PM5100 is housed in a robust casing that ensures long-term reliability and durability.
  • Compact Size: Its compact design allows for easy installation in existing electrical panels without requiring significant space.

Applications of METSEPM5100

The METSEPM5100 is suitable for a variety of applications, including:

  • Industrial Facilities: In industrial settings, the PM5100 helps monitor and optimize energy usage, ensuring machinery and equipment operate efficiently.
  • Commercial Buildings: For commercial buildings, the meter provides valuable insights into energy consumption patterns, aiding in the reduction of energy costs and the improvement of overall building efficiency.
  • Educational Institutions: Schools and universities can use the PM5100 to track energy usage across different buildings and departments, supporting energy-saving initiatives.
  • Retail and Hospitality: In retail stores and hotels, monitoring energy usage can lead to significant cost savings and support sustainability goals.

Benefits of Using METSEPM5100

Cost-Effective Energy Management

The PM5100 provides the essential data needed to manage energy consumption effectively, helping to identify areas where energy use can be reduced. This can lead to substantial cost savings over time.

Enhanced Operational Efficiency

By providing accurate measurements of key electrical parameters, the PM5100 helps ensure that electrical systems are operating efficiently. This can prevent energy waste, reduce the risk of equipment damage, and extend the lifespan of electrical components.

Simple and Reliable Monitoring

The straightforward design of the PM5100 makes it easy to install and use. Without the need for communication features, it offers a reliable solution for basic power and energy monitoring needs.

Installation and Configuration

Easy Installation

The METSEPM5100 is designed for hassle-free installation in electrical panels. It supports both direct and CT (current transformer) connections, making it adaptable to various system configurations.

Simplified Configuration

The meter can be configured using the front panel interface, allowing users to quickly set up the meter to meet their specific monitoring requirements. The intuitive setup process minimizes the time and effort needed to get the meter up and running.

Frequently Asked Questions (FAQs)

What are the main functions of the METSEPM5100?

The METSEPM5100 provides accurate measurements of voltage, current, power (active, reactive, and apparent), energy, and power factor, allowing for effective monitoring of electrical systems.

Does the PM5100 support communication features?

No, the PM5100 is designed without communication capabilities, focusing on delivering essential measurement functions for straightforward power and energy monitoring.

How accurate is the METSEPM5100?

The PM5100 offers high accuracy for all measured parameters, ensuring reliable data for energy management and system optimization.

Can the PM5100 be used in industrial environments?

Yes, the PM5100 is built to withstand the demands of industrial environments, offering durable construction and reliable performance.

Is the PM5100 suitable for commercial buildings?

Yes, the PM5100 is ideal for commercial buildings, providing valuable insights into energy consumption patterns and helping to reduce energy costs.

Conclusion

The METSEPM5100 PowerLogic PM5000 series meter by Schneider Electric is a reliable and accurate tool for monitoring electrical systems. With its high-accuracy measurements, user-friendly interface, and robust design, the PM5100 is an excellent choice for applications where straightforward, reliable power and energy monitoring is required. Whether used in industrial facilities, commercial buildings, or other settings, the PM5100 helps enhance operational efficiency, manage energy consumption effectively, and ensure the reliability of electrical systems.