Main
range of productPowerLogic PM700.
device short namePM750.
product or component typePower meter.
Complementary
power quality analysisTotal harmonic distortion.
type of measurementCurrent.
Voltage.
Frequency.
Power factor total..
Apparent power total.
Active power total.
Reactive power total.
Apparent power per phase.
Active power per phase.
Reactive power per phase.
Energy.
supply voltage125…250 V DC.
115…415 V AC 45…65 Hz.
network frequency45…65 Hz.
maximum power consumption in VA5 VA
display typeBacklit LCD.
display resolution6 lines.
sampling rate32 samples/cycle.
measurement current5 A.
1 A.
input typeCurrent: 0.005…6 A (impedance <= 0.1 Ohm).
measurement voltage10…480 V AC 45…65 Hz, phase to phase.
10…277 V AC 45…65 Hz phase to neutral.
number of inputs2 digital.
measurement accuracyFrequency: 0.02 Hz, 45–65 Hz.
Power factor: 0.0034, 1A to 6A, and from -0.5 to +0.5.
Current 0.4% 1…6 A.
Voltage: 0.3%, 50–227 V.
Power: 0.5%.
accuracy classClass 2 reactive energy conforms to IEC 62053-23.
Class 0.5S active energy conforms to IEC 62053-22.
Class 0.5 active energy conforms to ANSI C12.20.
number of outputs1 digital (static).
communication port protocolModbus 19.2 kbauds.
communication port supportRS485.
data recordingAlarms
Min/max of instantaneous values.
Environment
electromagnetic compatibilityLimits for harmonic current emissions: conforming to IEC 61000-3-2.
Conducted and radiated emissions, conforming to EN 55011 class B.
Electrostatic discharge immunity test: class III, conforming to IEC 61000-4-2.
Susceptibility to electromagnetic fields: class III, conforming to IEC 61000-4-3.
Electrical fast transient/burst immunity test: class III, conforming to IEC 61000-4-4.
1.2/50 µs shock wave immunity test: class III, conforming to IEC 61000-4-5.
Conducted RF disturbances, class III, conforming to IEC 61000-4-6.
Immunity to impulse waves: class III, conforming to IEC 61000-4-8.
Immunity to microbreaks and voltage drops: class III, conforming to IEC 61000-4-11.
Limitation of voltage changes, voltage fluctuations, and flicker in low-voltage: conforming to IEC 61000-3-3.
mounting modeFlush-mounted.
mounting supportPanel.
type of installationIndoor installation.
overvoltage categoryIII
IP degree of protectionIP30 back: conforming to IEC 60529.
IP52 front face: conforming to IEC 60529.
relative humidity95 % at 50 °C.
pollution degree2
ambient air temperature for operation-5…50 °C.
ambient air temperature for storage-40…85 °C.
operating altitude0…3000 m.
standardsIEC 61010-1.
CSA C22.2 No. 14.
UL 508.
product certificationsCE.
cULus.
width96 mm.
depth69 mm.
height96 mm.
net weight0.37 kg.