LV431630 – circuit breaker ComPact NSX250F, 36 kA
Original price was: $487.00.$375.00Current price is: $375.00.
The LV431630 ComPact NSX250F circuit breaker from Schneider Electric offers a 36 kA breaking capacity for industrial and commercial applications.
3 in stock
Free shipping on orders over $5000!
- Satisfaction Guaranteed
- No Hassle Refunds
- Secure Payments
Description
range | ComPactHz,.. |
---|---|
product name | ComPact NSX250F. |
range of product | ComPact NSX100…250. |
device short name | NSX250F. |
product or component type | Circuit breaker. |
device application | Distribution. |
Number of poles | 3P. |
protected poles description | 2t. |
[In] rated current | 250 A at 40 °C. |
[Ue] rated operational voltage | 690 V AC 50/60 Hz. |
network type | AC. |
network frequency | 50/60 Hz. |
suitability for isolation | Yes conforming to EN/IEC 60947-2. |
utilisation category | Category A. |
[Icu] rated ultimate short-circuit breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508. 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2. 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2. 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2.. 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2. 35 kA at 480 V AC 50/60 Hz conforming to UL 508. 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2. 15 kA at 600 V AC 50/60 Hz conforming to UL 508. |
Performance level | F 36 kA 415 V AC. |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic. |
trip unit protection functions | LI. |
control type | Toggle. |
Circuit breaker mounting mode | Fixed. |
[Ui] rated insulation voltage | 800 V AC, 50/60 Hz. |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV. |
[Ics] rated service short-circuit breaking capacity | 35 kA at 440 V AC 50/60 Hz, conforming to IEC 60947-2. 36 kA at 380/415 V AC 50/60 Hz, conforming to IEC 60947-2. 85 kA at 220/240 V AC 50/60 Hz, conforming to IEC 60947-2. 22 kA at 525 V AC 50/60 Hz, conforming to IEC 60947-2. 30 kA at 500 V AC 50/60 Hz, conforming to IEC 60947-2. 8 kA at 660/690 V AC 50/60 Hz, conforming to IEC 60947-2. |
mechanical durability | 20000 cycles. |
electrical durability | 5000 cycles at 690 volts 10000 cycles at 690 V In/2. 10000 cycles at 440 V. 20000 cycles at 440 V In/2. |
mounting support | Backplate. |
upside connection | Front. |
downside connection | Front. |
connection pitch | 35 mm. |
protection type | L: for overload protection (thermal). I: for short-circuit protection (magnetic). |
trip unit rating | 250 A at 40 °C. |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable. |
[Ir] long-time protection pick-up adjustment range | 0.7…1 x In. |
Long-time protection delay adjustment type tr | Fixed. |
[tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In. 15 s at 6 x Ir. |
Short-time protection pick-up adjustment type Isd | Adjustable. |
[Isd] Short-time protection pick-up adjustment range | 5…10 x In. |
Short-time protection delay adjustment type tsd | Fixed. |
earth-leakage protection | Without. |
Number of slots for electrical auxiliaries | 5 slot(s). |
Width (W) | 105 mm |
Height (H) | 161 mm. |
Depth (D) | 86 mm. |
net weight | 2.4 kg. |
standards | EN/IEC 60947. |
---|---|
product certifications | Marine. EAC CCC.. |
overvoltage category | Class II. |
electrical shock protection class | Class II. |
pollution degree | conforming to IEC 60664-1. |
IP degree of protection | IP40 conforms to IEC 60529. |
IK degree of protection | IK07 conforms to IEC 62262. |
ambient air temperature for operation | -25…70 °C. |
ambient air temperature for storage | -50…85 °C. |
relative humidity | 0…95 %. |
operating altitude | 0..2000 m without derating. 2000 m…5000 m with derating. |
Package 1: Weight | 1.999 kg. |
---|---|
Package 1: Height | 14.200 cm. |
Package: 1 width | 11.600 cm. |
Package 1 Length | 19.300 cm. |
Sustainable offer status | Green premium product. |
---|---|
REACh Regulation | REACh Declaration. |
EU RoHS Directive |
Compliant.
EU RoHS Declaration. |
Mercury free | Yes. |
RoHS exemption information | Yes. |
China’s RoHS Regulation | China RoHS declaration.
Product out of China’s RoHS standard. Substance declaration for your information.
|
Environmental Disclosure | Product Environmental Profile. |
Circularity Profile | End-of-life information. |
WEEE | The product must be disposed of on European Union markets. following specific waste collection and never end up in rubbish bins. |
California proposition 65 | Warning: This product can expose you to chemicals including DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. |