Sale!

59658 Ethernet Ports Interface

Original price was: $624.00.Current price is: $480.00.

The 59658 – 2 Ethernet ports interface module is designed for industrial applications, offering dual Ethernet ports for reliable and flexible network connectivity.

5 in stock

Category:

Description

 

Description

Main
RANGE OF PRODUCT Sepam Series 40.
Sepam Series 80 NPP.
Sepam series 60.
Sepam Series 80.
DEVICE SHORT NAME ACE850TP
Complementary
COMMUNICATION PORT PROTOCOL ARP network: S-LAN and E-LAN interfaces: 2 Ethernet ports: 10/100BASE-TX.


FTP network: S-LAN and E-LAN interfaces: 2 Ethernet ports 10/100BASE-TX.


HTTP network: S-LAN and E-LAN interface: 2 Ethernet ports 10/100BASE-TX.


IEC 61850 network: S-LAN and E-LAN interface: 2 Ethernet ports 10/100BASE-TX.


Modbus RTU network: S-LAN and E-LAN.

interface: 2 Ethernet ports (10/100BASE-TX).


Modbus TCP/IP network: S-LAN and E-LAN.

interface: 2 Ethernet ports (10/100BASE-TX).


RSTP 801.1d 2004 network: S-LAN and E-LAN.

interface: 2 Ethernet ports (10/100BASE-TX).


SNMP network: S-LAN and E-LAN interfaces: 2.

Ethernet ports 10/100BASE-TX.


SNTP network: S-LAN and E-LAN interface: 2 Ethernet ports 10/100BASE-TX.

 

LOCAL SIGNALLING Green LED1 for energized (front face).


Green LED2 for communication status OK (front face).


Green LED3 off for port 2 Ethernet 10 Mbit/s (front face).


Green LED3 on for port 2 Ethernet 100 Mbit/s (front face).


Green LED4 flashing for port 2 Ethernet sending data and receiving data (front face).


Green LED5 off for port 1 Ethernet 10 Mbit/s (front face).


Green LED5 on for port 1 Ethernet 100 Mbit/s (front face).


Green LED6 flashing for port 1 Ethernet sending data and receiving data (front face).


Red LED1 flashing for not set up or not base-unit connected (front face).


Red LED1 is off for de-energized (front face).


Red LED1 remains ON for fault (front face).

 

[US] RATED SUPPLY VOLTAGE 110…240 V AC tolerance: -20…10%.
24…250 V DC tolerance: 20…10%.
MOUNTING MODE Fixed.
MOUNTING SUPPORT Symmetrical DIN rail.
HEIGHT 127 mm
WIDTH 171 mm
DEPTH 58 mm
PRODUCT WEIGHT 0.4 kg
MECHANICAL ROBUSTNESS Earthquakes in operation (level 2): 1 Gn. (vertical axes) conforming to IEC 60255-21-3.


Earthquakes in operation (level 2): 2 Gn.

(horizontal axes) conforming to IEC 60255-21-3.


Jolts de-energized (level 2): 20 Gn/16 ms., conforming to IEC 60255-21-2.


Shocks de-energized (level 2): 30 Gn/11 ms., conforming to IEC 60255-21-2.


Shocks in operation (level 2): 10 Gn/11 ms., conforming to IEC 60255-21-2.


Vibrations de-energized (level: 2) : 2 Gn, 10. Hz, 150 Hz, conforming to IEC 60255-21-1.


Vibrations in operation (level: 2) : 1 Gn, 10 Hz, 150 Hz, conforming to IEC 60255-21-1.


Vibrations in operation (level: Fc): 2 Hz… 13.2.

Hz, a = +/- 1 mm, conforming to IEC 60068-2-6.

 

MAXIMUM CABLE DISTANCE BETWEEN DEVICES <100 m.
AUXILIARY CONNECTION TERMINAL Functional earth: ring lug, 1 pin(s), 1 cable(s), tinned copper braid, 4 mm2.


Protective earth: screw-type connector 1 pin(s) 1 cable(s) wire 2.5 mm² <3 m.


Supply: screw-type connector, 3 pin(s), 1 cable(s), wire, 0.5–2.5 mm2.


Supply: screw-type connector, 3 pin(s), 1 cable(s), 1.5 mm2.


Supply: screw-type connector, 3 pin(s), 1 cable(s), 2.5 mm2.


Supply: screw-type connector, 3 pins, 2 cable(s), wire, 0.5… 1 mm2.


Supply: screw-type connector, 3 pins, 2 cable(s), 1 mm2.


Supply: screw-type connector, 4 pin(s), 1 cable(s), wire, 0.5…2.5 mm2.


Supply: screw-type connector, 4 pins, 1 cable(s), wire, 1.5 mm2.


Supply: screw-type connector, 4 pin(s), 1 cable(s), wire, 2.5 mm2.


Supply: screw-type connector, 4 pins, 2 cable(s), wire, 0.5… 1 mm2.


Supply: screw-type connector, 4 pins, 2 cable(s), 1 mm².

WIRE STRIPPING LENGTH Supply: 8 mm.
Environment
ELECTROMAGNETIC COMPATIBILITY 1 MHz damped oscillating wave.

(immunity tests-conducted disturbances), 2.5 kV MC and MD, conforming to ANSI C37.90.1


1 MHz damped oscillating wave.

(immunity tests-conducted disturbances), III, 2.5 kV MC, 1 kV MD, conforming to IEC 60255-22-1.


100 kHz damped oscillating wave.

(immunity tests-conducted disturbances), 2.5 kV MC, 1 kV MD, conforming to IEC 61000-4-12.


Conducted disturbance emission.

(emission tests), conforming to IEC 60255-25.


Conducted disturbance emission.

(emission tests), B, conforming to EN 55022.


Disturbing field emission.

(emission tests), conforming to IEC 60255-25.


Disturbing field emission.

(emission tests), A, conforming to EN 55022.


Electrostatic discharge: (immunity tests-radiated disturbances).

8 kV air, 4 kV contact, conforming to ANSI C37.90.3.


Electrostatic discharge.

(immunity tests-radiated disturbances), 8 kV air, 6 kV contact, conforming to IEC 60255-22-2.


Fast transient bursts

(immunity tests-conducted disturbances), 4 kV, 2.5 kHz, conforming to ANSI C37.90.1.


Fast transient bursts

(immunity tests-conducted disturbances), A or B, 4 kV, 2.5 kHz/2 kV, 5 kHz, conforming to IEC 60255-22-4.


Fast transient bursts

(immunity tests-conducted disturbances), IV, 4 kV, 2.5 kHz, conforming to IEC 61000-4-4.


Immunity to conducted RF disturbances

(immunity tests-conducted disturbances), 10 V, conforming to IEC 60255-22-6.


Immunity to magnetic fields at network frequency: .(immunity tests-radiated disturbances).

 

 IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8.


Immunity to radiated fields

(immunity tests-radiated disturbances), 10 V/m, 80 MHz, 1 GHz, conforming to IEC 60255-22-3.


Immunity to radiated fields

(immunity tests-radiated disturbances), 35 V/m, 25 MHz, 1 GHz, conforming to ANSI C37.90.2 (1995).


Immunity to radiated fields

(immunity tests-radiated disturbances), III, 10 V/m, 80 MHz, 2 GHz, conforming to IEC 61000-4-3.


Surges

(immunity tests-conducted disturbances), III, 2 kV MC, 1 kV MD, conforming to IEC 61000-4-5
Voltage interruptions.

(immunity tests-conducted disturbances), 100%, 10 ms, conforming to IEC 60255-11.

CLIMATIC WITHSTAND Influence of corrosion/gaz test 4 (in operation).

21 days, 75% RH, 25 °C, 0.01 ppm H2S, 0.2 ppm. S02, 0.02 ppm NO2, and 0.01 ppm Cl2 conforming to IEC 60068-2-60.
Continuous exposure to damp heat (in operation).

Ca: 10 days, 93% RH, 40 °C (104 °F), conforming to IEC 60068-2-3.


Continuous exposure to damp heat (in storage)

Ca: 56 days, 93% RH, 40 °C (104 °F), conforming to IEC 60068-2-3.


Exposure to cold (in operation).

Ab: -25 °C (- 13 °F) conforming to IEC 60068-2-1.


Exposure to cold (in storage) : Ab: -25 °C (- 13 °F) conforming to IEC 60068-2-1.
Exposure to dry heat (in operation) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2.


Exposure to dry heat (in storage) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2.


Influence of corrosion/gaz test 2 (in operation) : 21 days, 75 % RH, 25 °C (- 13 °F), 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60.


Salt mist (in operation) : Kb/2, conforming to IEC 60068-2-52.


Temperature variation with specified variation rate (in operation).

Nb: -25 °C to 70 °C (- 13 °F to 158 °F) 5 °C/min (41 °F/min), conforming to IEC 60068-2-14.

AMBIENT AIR TEMPERATURE FOR OPERATION -25…70 °C.
Packing Units
UNIT TYPE OF PACKAGE 1 PCE
NUMBER OF UNITS IN PACKAGE 1 1
PACKAGE 1 HEIGHT 9.800 cm
PACKAGE 1 WIDTH 16.700 cm
PACKAGE 1 LENGTH 19.800 cm
PACKAGE 1 WEIGHT 721 g
UNIT TYPE OF PACKAGE 2 S03
NUMBER OF UNITS IN PACKAGE 2 6
PACKAGE 2 HEIGHT 30.000 cm
PACKAGE 2 WIDTH 30.000 cm
PACKAGE 2 LENGTH 40.000 cm
PACKAGE 2 WEIGHT 4.733 kg
UNIT TYPE OF PACKAGE 3 P12
NUMBER OF UNITS IN PACKAGE 3 48
PACKAGE 3 HEIGHT 44.500 cm
PACKAGE 3 WIDTH 80.000 cm
PACKAGE 3 LENGTH 120.000 cm
PACKAGE 3 WEIGHT 49.784 kg

The 59658-22 Ethernet Port Interface Module is typically used in industrial and automation environments to provide Ethernet connectivity for devices and systems. This module allows devices to communicate over Ethernet networks, enabling data exchange, remote monitoring, and control in various applications.

Key Features:

  1. Dual Ethernet ports:
    • The module comes with two Ethernet ports, which can be used for various purposes, such as redundant networking, daisy-chaining devices, or connecting to different networks.
  2. Network Protocols:
    • Supports standard Ethernet protocols such as TCP/IP, UDP, and possibly industrial protocols like Modbus TCP, PROFINET, or EtherNet/IP, allowing seamless integration with existing network infrastructure.
  3. Data Transfer Rates:
    • Typically, it supports standard Ethernet speeds, such as 10/100 Mbps or even Gigabit Ethernet (1000 Mbps) in some models, ensuring fast and reliable data communication.
  4. Rugged Design: