STBACI8320K – analog input kit, Modicon STB, standard
Original price was: $384.00.$295.00Current price is: $295.00.
The STBACI8320K analog input kit from Schneider Electric’s Modicon STB series offers multiple input channels for precise measurement of analog signals,
3 in stock
Free shipping on orders over $5000!
- Satisfaction Guaranteed
- No Hassle Refunds
- Secure Payments
Description
range of product | Modicon STB distributed I/O solution. |
---|---|
product or component type | Standard analog input kit. |
kit composition | STBACI8320 module. STBXBA2000 base. STBXTS1100, 6-terminal screw type connector. STBXTS2100, 6-terminal spring clamp connector. |
analogue input type | Current 0…20 mA. Current 4…20 mA. |
analogue input number | 4 |
communication port protocol | Hart protocol tolerance. |
analogue input resolution | 15 bits + sign. |
type of filter | Single low pass input filter 985 Hz. |
absolute maximum input | 25 mA/50 V DC. |
---|---|
cold swapping | Yes |
hot swapping fallback | Yes for standard NIMs. |
fallback status | State 0 basic NIMs. User configurable standard NIMs. |
data format | EN 61131-2. IEC 61131-2. |
update time | 80 ms |
integral linearity | +/- 0.05 %FS. |
input impedance | 250 Ohm |
maximum supply current for sensors | 25 mA per input channels. |
protection type | Short-circuit protection. |
absolute accuracy error | +/- 0.4 % of full scale 25 °C. |
temperature drift | +/-0.005 %/°C. |
insulation between channels and logic bus | 1780 V for 1 minute. |
insulation between channels and sensor bus | 200 V. |
addressing requirement | 8 input words. |
product compatibility | Power distribution module. Mounting base: STBXBA2000. |
[Us] rated supply voltage | 24 V DC |
supply | Power distribution module. |
current consumption | 95 mA at 5 V DC for the logic bus. |
marking | CE. |
overvoltage category | II. |
status LED | 1 LED (green) module status. (RDY). 1 LED (red) module error (ERR). |
depth | 70 mm |
height | 18.4 mm |
width | 128.3 mm |
product certifications | CSA C-Tick ATEX Cat 3G FM Class 1 Division 2. UL |
---|---|
pollution degree | conforming to IEC 60664-1. |
operating altitude | <= 2000 m |
IP degree of protection | IP20 conforms to EN 61131-2 class 1. |
ambient air temperature for operation | -25…70 °C. |
ambient air temperature for operation | 32–140 °F without derating. |
ambient air temperature for storage | -40…85 °C without derating. |
ambient air temperature for storage | -40–185 °F without derating. |
relative humidity | 95 % at 60 °C without condensation. |
vibration resistance | +/-0.35 mm at 10…58 Hz. 3 gn at 58…150 Hz on 35 x 7.5 mm symmetrical DIN rail. 5 gn at 58…150 Hz on 35 x 15 mm symmetrical DIN rail. |
shock resistance | 30 gn for 11 ms, conforming to IEC 88 reference 2-27. |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Weight | 146.0 g |
Package 1 Height | 3 cm |
Package 1 width | 8 cm |
Package 1 Length | 13 cm |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 28 |
Package 2 Weight | 4.599 kg |
Package 2 Height | 15 cm |
Package 2 width | 30 cm |
Package 2 Length | 40 cm |
Unit Type of Package 3 | PAL |
Number of Units in Package 3 | 448 |
Package 3 Weight | 65.408 kg |
Package 3 Height | 60 cm |
Package 3 width | 80 cm |
Package 3 Length | 448 cm |