Description
range of product | Modicon Quantum automation platform. | |
---|---|---|
product or component type | Analogue input module. |
analogue input number | 8. | |
---|---|---|
input type | Differential. | |
addressing requirement | 9 input words. | |
analogue input type | Temperature probe: 100–450 °C. Pt 100, Pt 200, Pt 500, and Pt 1000. Temperature probe: 200–850 °C. Pt 100, Pt 200, Pt 500, and Pt 1000. Temperature probe: 60–180 °C Ni 100, Ni 200, Ni 500, and Ni 1000. Temperature probe: 0.5 mA Ni 100, Ni 200, Ni 500, and Ni 1000. Temperature probe: 2..5 mA Pt 100, Pt 200, Ni 100, Ni 200 | |
analogue input resolution | 13 bits | |
input impedance | >= 10 MOhm. | |
absolute accuracy error | 0.1 °C | |
linearity error | +/- 0.01% full scale. +/- 0.5 °C | |
accuracy drift according to temperature | +/- 0.5 °C at 77 °F (25 °C). +/- 0.9 °C at 32…140 °F (0…60 °C). | |
isolation between channels and bus | 2500 V DC for 60 s. 1780 V AC 47.63 Hz for 60 s. | |
isolation between channels | 300 Vrms AC. | |
update time | 1200 ms, 3 wires. 640 ms, 2 wires, 4 wires. | |
fault type | Broken wire. Overtacking scale. | |
marking | CE | |
local signalling | 1 LED green bus communication is present. (Active). 1 LED-red external fault. 8 LED green channels are turned on. 8 LEDs with a red channel fault. | |
bus current requirement | 200 mA | |
power dissipation in W | 1 W. | |
module format | Standard. | |
product weight | 0.66 lb (US) (0.3 kg). |
standards | CSA C22.2 No. 142. UL 508. | |
---|---|---|
product certifications | CUL FM Class 1 Division 2. | |
resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2. 8 kV on air, conforming to IEC 801-2. | |
resistance to electromagnetic fields | 9.14 V/yd (10 V/m) 80…1000 MHz, conforming to IEC 801-3. | |
ambient air temperature for operation | 32…140 °F (0…60 °C). | |
ambient air temperature for storage | -40.185 °F (-40.85 °C). | |
relative humidity | 95% without condensation. | |
operating altitude | <= 16404.2 ft (5000 m). |