140CPU43412U – Unity processor Modicon Quantum
Original price was: $5,655.00.$4,319.00Current price is: $4,319.00.
The 140CPU43412U is a high-performance Unity processor from the Modicon Quantum series, designed for complex industrial automation.
13 in stock
Free shipping on orders over $5000!
- Satisfaction Guaranteed
- No Hassle Refunds
- Secure Payments
Description
Â
| range of product | Modicon Quantum automation platform. | |
|---|---|---|
| product or component type | Unity processor. |
| clock frequency | 66 MHz. | |
|---|---|---|
| number of slots | 10 4 16 2 6 | |
| number of racks | 2: local rack(s). | |
| number of distributed I/O station | 63 station(s) 1 rack(s) 3 Modbus Plus network(s). | |
| number of remote I/O station | 31: 2 S908 remote I/O rack(s). 0–0 ethernet remote I/O rack(s). | |
| discrete I/O number | 8000 inputs, 8000 outputs, distributed per network (Modbus Plus). Unlimited (26 slots max): local. 31744 inputs, 31744 outputs, remote. | |
| analogue I/O number | Unlimited (26 slots max): local. 1984 inputs, 1984 outputs: S908 remote I/O. 500 inputs and 500 outputs are distributed per network (Modbus Plus). | |
| application specific I/O | Counter. Serial link. High-speed interrupt inputs. Accurate time stamping. | |
| number of optional modules | 6 (Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max). | |
| maximum number of connections | 2 (AS-Interface): distributed. 2 (Modbus): RS232/485 Modbus/ASCII. 4 (AS-Interface): remote. 6 (Ethernet TCP/IP): local. 6 (Modbus Plus): local. 6 (Profibus DP): local. | |
| integrated connection type | 1 Modbus Plus with. 2 Modbus with. | |
| checks | Process control. | |
| memory description | Internal RAM: 1056 kB. | |
| switch function | Key switch memory starts or stops memory protection. Slide switch communication port: ASCII/RTU/Memory. | |
| application structure | 1 cyclic/periodic master task: 1 periodic fast task. 16-timer interrupts tasks. 64 I/O interrupt tasks. 64 interrupt tasks. There are no auxiliary tasks. | |
| execution time per instruction | 0.1–0.27 µs floating points. 0.1–0.27 µs on fixed-point arithmetic. 0.12…0.585 µs Boolean. 0.12…0.585 µs on word. | |
| number of instructions per ms | 1.86 Kinst/ms if 100% Boolean. 2.49 Kinst/ms is 65 % boolean and 35 % numerical. | |
| system overhead | 1 ms: master task. 0.2 ms: fast task. | |
| bus current requirement | 1800 mA. | |
| local signalling | 1 LED green communications are active on the Modbus Plus port (Modbus Plus). 1 LED green communications are active on the Modbus port. 1 LED green CPU has been started and is solving logic (RUN). 1 LED green CPU has passed the power-up diagnostic tests (READY). 1 LED orange write-protected memory (memory port) 1 LED red battery needs replacing or is not present (BAT LOW). 1 LED red communications error on the Modbus Plus port (ERROR A). | |
| electrical connection | 1 female connector, connector type: SUB-D 9, for connecting to the Modbus Plus network. 2 female connectors, connector type: SUB-D 9, for connecting to the Modbus bus. |
| product certifications | UL. CSA CE | |
|---|---|---|
| standards | HazLoc. |
| Category | 18150: Quantum Controllers, HSWY, and Comm. | |
|---|---|---|
| Discount Schedule | PC21 | |
| GTIN | 00785901421078. | |
| Nbr. of units in pkg. | 1 | |
| Package weight(Lbs) | 1.3500000000000001. | |
| Returnability | N | |
| Country of origin | FR |